SiCOMS® – Failure in SiCOMS® Sensors

The display shows “Err.Sens.xx: nnnn [text error message]”

with       xx: sensor number, for example 01

              nnnn: error code (refer to the following table)

Error codesError descriptionHelp
0001must value for IR transmitter LED too high (> 3000)IR track must be cleaned and sensor must be recalibrated. If the error persists after recalibration, it means that the IR transmitter system is defect. Sensor must be exchanged and repaired by the manufacturer.
0002must value for IR transmitter LED too low (< 100)
0004calibration of IR measuring track is falseIR track must be cleaned and sensor must be recalibrated. If the error persists after recalibration, it means that the IR measuring track has not the right IR transmission and is defect. Sensor must be exchanged and repaired by the manufacturer.
0008Transmission of IR measuring track too high (Opacref > 1170)  
0010(“LT dirty”) Transmission of IR measuring track too low (Opacref < 400)Sensor must only be cleaned, NOT calibrated !!
Error codesError descriptionHelp
0020Transmission of IR measuring track too high. If transmitter LED is off, this means that receiver is receiving IR noise from other equipment, which can only be if the sensor is not mounted in the SOG !!Sensor cannot be operated in this environment (IR noise) without SOG. Insert sensor in the SOG and restart evaluator.
0040Temperature of the IR track/ sensor front too low ( < -7 °C )Check the displayed temperature value for this sensor in the “Sensor values” menu of the evaluator. If the value is -99 or 999, the built-in temperature chip is defect, the sensor must be exchanged and repaired by the manufacturer. If the displayed value is feasible at the actual environment of sensor, the sensor is used out of specified temperature range. The error is reset automatically when the sensor temperature is back within the specification range.
0080Temperature of the IR track/ sensor front too high ( > 117 °C)
0100Temperature of sensors CPU too high (> 95 degree)The sensor CPU temperature is too high. The housing of the sensor must be cooled using airstream.
0200Temperature of  sensors CPU too low (< -5 degree)The sensor CPU temperature is too low. The housing of the sensor must be heated up using airstream.
0400Sensor is in power-up mode after system restartDisappears automatically after approx. 10 seconds

If multiple errors are detected, the error code is calculated as the hexadecimal sum
of individual error codes. Text message for the first detected error code is shown
after the sum error code.