SiCOMS® – Evaluator Failure

The display shows “OMD – Error nnnn!”

with  nnnn:  error code (refer to the following table)

Error codeError descriptionHelp
0001No sensor detected• Check cables
• Is the number of sensors set up correctly?
0002Date and time invalid in real-time clock• Set date and time
• If the error occurs again, replace Evaluator
0004Failure in event memoryRead out memory and reinitialise the Evaluator

If multiple errors are detected, the error code is calculated as the hexadecimal sum of individual error codes.