BeCOMS® – Setup Parameter

Menu level 1Menu level 2Menu level 3Description

Setup Parameter
Setup Parameter
 View and change BeCOMS® parameters.
 
If the sublevel was entered (see Table 1 on page 4.9), pressing [Esc] restarts the Evaluator
 
To get write access to these parameters, a PIN
must be entered (see Table 2 on page 4.11)

Table 1 Setup Parameter Details

Menu level 1Menu level 2Menu level 3Description


TS Alm-Level DC TS Alm-Level DCThe value of DC main alarm level in the range of 0 to 5. The higher the value, the less sensitive is the system. The 0 value disables the DC alarm.
TS PreAlm-Level
TS PreAlm-Level
The value of DC pre-alarm level in percents of DC main alarm.
Possible values: 40 to 100.
RPM Alarm-Level
RPM Alarm-Level
The value of overspeed alarm in RPM.
Possible values: 0 to 3000, step 50.
The 0 value disables the alarm.
TS Alm-Level1 AC
TS Alm-Level1 AC
The value of AC main alarm level in the RPM zone 1.
Possible values: 0 to 5.
The 0 value disables the alarm.
TS Alm-Level2 AC
TS Alm-Level2 AC
The value of AC main alarm level in the RPM zone 2.
Possible values: 0 to 5.
The 0 value disables the alarm.
RPM for Level2
RPM for Level2
Engine rotation speed in RPM which defines the boundary between RPM
zone 1 and RPM zone 2.
Start Alminhibit
Start Alminhibit
Time interval in seconds immediately after engine start during which the main alarm is disabled.
TS Test Time
TS Test Time
Time interval between test pulses, possible values: 1 min to 10 min.
Test pulses help to check if the SRE sensor functions correct.
TS Test Len
TS Test Len
The length of test pulse.
Possible values: 1 s to 15 s.
IS Impuls Offset
IS Impuls Offset
The offset between TDC of cylinder 1 and the synchronisation pulse at
the channel 0.
 
This value cannot be set at the Evaluator using the “Up” and “Down” buttons. It is used during the impulse offset setup procedure as an indicator.
 
To start the procedure, a PIN must be entered (refer to Table 2 on page 4.11)
PIN Impuls Offs
PIN Impuls Offs
PIN for impulse offset setup, the procedure is the same as described in Table 2 on page 4.11
TSeff ena for DC
TSeff ena for DC
Enable or disable (values 1 and 0 accordingly) calculating effective value of thermosignal in percents of DC alarm level.
Values for TSeff
Values for TSeff
Number of points for calculating effective value of thermosignal in percents
of DC alarm level.
DC Alarm percent
Values for TSeff
Scale factor for DC alarm level, possible values: 80% to 199%.
AC Alarm percent
AC Alarm percent
Scale factor for AC alarm level, possible values: 80% to 199%.