SiCOMS® – Communication Failure

The display shows “Err.Sens.xx Stat: nn”

with       xx: sensor number, for example 01
            nn: error code (refer to the following table)

Error codeError descriptionHelp
01Sensor does not respond via interface “loop out” (connector 4)Restart system by pressing the ESC button
02Sensor does not respond via interface “loop in” (connector 5)
03Sensor does not respond at all
13Sensor will not be read any longer
20Sensor initialising error
(connectors see Appendix Fig 12.11)

If multiple errors are detected, the error code is calculated as the hexadecimal sum of individual error codes. For example:

The message “Err.Sens.02 Stat: 33” includes the error codes 13 and 20. The meaning of the error message is: sensor 02 cannot be initialised and will not be read.

If the failure persists after restarting, the sensor causing the failure can be detected using the menu “Sensor values”:

Start menu “Sensor values”, select one sensor after another:

The circuit is broken between sensors when sensor status switches from 01 to 02:

E.g.:    Sensor 01: Status 01
            Sensor 02: Status 01
            Sensor 03: Status 01
            Sensor 04: Status 02

The circuit is broken here between sensor 03 and sensor 04. Check wiring.